Successful 12 volt trigger with adequate delay

I was not too sure where to post this. 12 volt trigger threads seemed old so I started a new one.

Context: ZP90 hooked to a Rotel power amp. I want Rotel to go on standby when no music is played. I read multiple threads and the consensus seems to be that this type of integration is either costly or not reliable due to extended silence between tracks in some records.

Here is what I did:

Parts:
Xantech Current sensing block CSM1
Xantech Power supply 781RG
Xantech Audio Sensor Module SMAUD01
Altronix 6062 Multipurpose timer

Total Canadian landed cost $110

I originally installed the Xantech components only. So when music was sensed, a 12 volt trigger would fire to the rotel amp. I quickly found the solution to be unusable as the Xantech timer is only 15 seconds and probably less and therefore the amp would trigger on-off multiple times either at end of a track or during silent parts of classical music.

I then added the Altronix timer. This is where it came all together.

When audio is sensed, Xantech send the 12 volt trigger to the Altronix, The Altronix send the 12 volt trigger to the Amp. I set the Altronix to 60 minutes delay so I need complete silence for 60 minutes before the Altronix releases the 12 volt signal. Now setting of the DIP switches is key here:

You want DIPs
1 OFF
2 OFF
3 ON
4 ON

With the DIP switches set that way, it ensure that :

1-Altronix energizes 12 volt as soon as it receives the 12 volt trigger from Xantech. In other words at start of timming cycle
2-Timer is set in minutes not seconds
3-Operating voltage is 12 volt not 24
4-Timing starts after the removal of trigger input. **this one is critical**

DIP switch 1 and 4 are key here: they will ensure that amp Altronix sends a 12 volt trigger as soon as audio is sensed AND DIP 4 plays a timer reset role. When music stops in between track and restarts, this restarts the timer for a new 60 minutes without releasing the 12 volt trigger.


Wiring.


Xantech power supply feeds the Xantech Current sensing block. Xantech current block has + and -. I used those to feed the + and - of Altronix

I plugged a wire between the Xantech current sensing block
"pull up" to the "TRG" of the Altronix

Plugged a wire from Altronix "+" to Altronix "C"

The wire pair going from the Altronix to the Rotel 3.5mm 12volt trigger has the negative to the "-" and the positive to the "NO"

I highly encourage that you try this with a multimeter first, you do not want to fry your amp. Once everything is working well offline then you may integrate
    This topic has been closed for further comments. You can use the search bar to find a similar topic, or create a new one by clicking Create Topic at the top of the page.

    25 replies

    Contributor I
    Aug 25, 2013 6:13 PM UTC
    Further to my earlier above post I would just like to comment that the J3 jumper needs to be cut on the Altronix 6062 to enable correct operation.
    My final setup is as per UPGRADEALWAYS Xantech & Altronix components but using Elan Audio Sensor as the Xantech audio sensor is currently discontinued.
    As additional comment the Elan sensor works opposite to Xantech and as such the PULL DOWN contact needs to be used on the CBCSM1. I have set the Elan to max sensitivity and this then switches when the volume is set to 25% and audio is playing on the Connect.
    As a matter of interest I use the above Connect "12V trigger" signal to switch a relay which turns on / off 2 x 400W RMS Alto powered speakers + mixer.
    I can provide a drawing or further information if anyone is interested.
    Translate
    Contributor I
    Oct 10, 2013 6:12 PM UTC
    Just a note of thanks to UPGRADEALWAYS. The trigger is working well, no clicking noises. THANKS
    Translate
    Avid Contributor I
    Oct 11, 2013 11:49 AM UTC
    Just a note of thanks to UPGRADEALWAYS. The trigger is working well, no clicking noises. THANKS

    Cool I m glad it works !
    Translate
    Lyricist II
    Dec 24, 2013 1:02 PM UTC
    Hello upgradealway. I just bought the Sonos Connect Amp and I’m bit of an electronics novice as you will soon see below. Can you please take a look and let me know if this follows your instructions exactly? Thanks …

    Buy:
    Xantech Current sensing block CBCSM1
    Xantech Power supply 781RG
    Xantech Audio Sensor Module SMAUD01
    Altronix 6062 Multipurpose timer

    Set DIPs:
    1 OFF, 2 OFF, 3 ON, 4 ON

    Wiring:
    [Using CAT-6 wire for everything]
    Xantech “+12VDC” to Altronix “+”
    Xantech “GND” to Altronix “-“ (not sure if this is correct)
    Xantech “Pull Up” to Altronix “TRG”
    Altronix “+” to Altronix “C”
    Altronix “-“ to Amp “GND” (not sure if this is correct)
    Altronix “NO” to Amp “12V” (not sure if this is correct)
    Translate
    Lyricist II
    Dec 28, 2013 2:46 PM UTC
    I addressed this to upgradealways, but maybe someone else can help.

    When upgradealways said in the wiring instructions that "Xantech current block has + and -. I used those to feed the + and - of Altronix".

    The Xantech has four inputs, 12vDC, GND, Pull Up, and Pull Down. Can I assume 12vDC is the "+" and GND is the '-'?

    I apologize in advance for the potentially stupid question.
    Translate
    buzz
    Grand Maestro
    Dec 29, 2013 3:20 PM UTC
    JohnL22a,

    "GND", "Ground", and "-" usually mean the negative power supply connection. As does the
    code:
      | 
    |
    -----
    ---
    -

    symbol.

    "+", "PWR", or a specific voltage such as "+12VDC", usually imply the positive power supply connection. However, a "+12VDC" terminal could also be some sort of output provided by the box. Offshore companies are often language challenged while writing instructions and labeling terminals.

    In any case, your wiring diagram is correct -- assuming that the "12V" terminal on the amplifier is its "12V Trigger" input.

    Which model amplifier are you using?
    Translate
    Lyricist II
    Dec 30, 2013 8:39 PM UTC
    Thanks for the help buzz. I appreciate it.

    My amp is a Parasound with two connections; +12V and GND. It looks like based on upgradealways initial wiring instructions and your help, I should hook the amp up as follows:
    Altronix “-“ to Amp “GND”
    Altronix “NO” to Amp “+12V”

    Makes sense?
    Translate
    buzz
    Grand Maestro
    Dec 31, 2013 2:01 AM UTC
    JohnL22a,

    Yes, as long as that "12V" terminal is a control input.
    Translate
    Lyricist I
    Mar 28, 2014 10:53 PM UTC
    hello all:

    i'm using two Sonos Amps, a speaker splitter and one Dayton SA230 sub amp to power an in-wall sub.

    is is possible to make a connection to the Dayton's 12v trigger so that when i use sonos the DAyton amp switches on?

    would an Elan Audio Sensor work? how would i connect the audio jack to the 12v trigger?

    thanks
    Translate
    buzz
    Grand Maestro
    Mar 29, 2014 12:11 AM UTC
    leib,

    First post! Welcome to the forums.

    You don't need any external equipment or additional connections. Set the Dayton SA230's "REMOTE TURN ON" to "Auto".
    Translate